Home » Vacuum Circuit Breaker »Outdoor Circuit Breaker » ZW7-40.5KV High Voltage 3 Poles Switches 35kV H.V. Outdoor Vacuum Circuit Breaker
  • ZW7-40.5 35kV outdoor vacuum circuit breaker
ZW7-40.5 35kV outdoor vacuum circuit breaker

ZW7-40.5KV High Voltage 3 Poles Switches 35kV H.V. Outdoor Vacuum Circuit Breaker

Model: ZW7-40.5

Description

The ZW7-40.5 outdoor high-voltage vacuum circuit breaker adopts a uniquely designed split pole and a highly reliable operating mechanism. The device is mainly used in medium-voltage overhead line power grids for dividing and combining load current, overload current, and short-circuit current.
  • General
  • Environmental conditions
  • Technical parameter
  • Drawing
The ZW7-40.5 outdoor high-voltage vacuum circuit breaker adopts a uniquely designed split pole and a highly reliable operating mechanism. The device is mainly used in medium-voltage overhead line power grids for dividing and combining load current, overload current, and short-circuit current.

Circuit breaker structure
ZW7-40.5 outdoor high-voltage vacuum circuit breaker is mainly composed of integrated pole, current transformer, operating mechanism and box. This type of circuit breaker is of miniaturized design, and the shell is made of high-quality steel box. Current transformers can be selected according to user needs. ZW7-40.5 outdoor high-voltage vacuum circuit breaker and matching intelligent control combination. The switch opening and closing operation can be realized locally, and it can also be remotely operated through the communication interface. Other information of the circuit breaker can also be transmitted to the control center, and the communication channel can choose cable, optical fiber, GPRS/CDMA, GSM, etc.

Features
1. Extremely high reliability
2. Completely maintenance-free throughout its lifetime
3. Has high mechanical and electrical life
4. The whole machine is small in size, light in weight, easy to install

1. Ambient air temperature: -30ºC~+60ºC;
2. Altitude: no more than 2000 meters;
3. The wind speed does not exceed 34m/s;
4. Vibration or ground motion from outside the switchgear and control equipment is negligible;
5. Contamination level: IV;
6. Storage temperature -40ºC~+85ºC.

S/N Item Unit Data
1 Rated voltage kV 40.5
2 Rated current A 1250/1600
3 Rated frequency Hz 50 or 60
4 Power frequency withstand voltage 1min (wet) (dry)

Phase-to-phase, to ground/fracture

kV 80 95/95
5 Lightning impulse withstand current (peak value)

Phase-to-phase, to ground/fracture

kV 185
6 Rated short-circuit breaking current kA 25/31.5
7 Rated short-circuit making current (peak) kA 63/80
8 Rated peak withstand current kA 63/80
9 4S short-time withstand current kA 25/31.5
10 Rated operating cycle O-0.1s – CO – 3s – CO – 6s CO- 60s recovery
11 Rated short-circuit current breaking times Times 30
12 Mechanical life Times 10000
13 Mechanism control voltage V AC/DC220
14 Secondary circuit 1min Power frequency withstand voltage kV 2

ZW7-40.5 35kV outdoor vacuum circuit breaker drawing

Get In Touch with Us


    Supported File : JPG, AI, PNG, PDF, CAD, JPEG