Circuit breaker structure
ZW7-40.5 outdoor high-voltage vacuum circuit breaker is mainly composed of integrated pole, current transformer, operating mechanism and box. This type of circuit breaker is of miniaturized design, and the shell is made of high-quality steel box. Current transformers can be selected according to user needs. ZW7-40.5 outdoor high-voltage vacuum circuit breaker and matching intelligent control combination. The switch opening and closing operation can be realized locally, and it can also be remotely operated through the communication interface. Other information of the circuit breaker can also be transmitted to the control center, and the communication channel can choose cable, optical fiber, GPRS/CDMA, GSM, etc.
1. Ambient air temperature: -30ºC~+60ºC;
2. Altitude: no more than 2000 meters;
3. The wind speed does not exceed 34m/s;
4. Vibration or ground motion from outside the switchgear and control equipment is negligible;
5. Contamination level: IV;
6. Storage temperature -40ºC~+85ºC.
S/N | Item | Unit | Data |
1 | Rated voltage | kV | 40.5 |
2 | Rated current | A | 1250/1600 |
3 | Rated frequency | Hz | 50 or 60 |
4 | Power frequency withstand voltage 1min (wet) (dry)
Phase-to-phase, to ground/fracture |
kV | 80 95/95 |
5 | Lightning impulse withstand current (peak value)
Phase-to-phase, to ground/fracture |
kV | 185 |
6 | Rated short-circuit breaking current | kA | 25/31.5 |
7 | Rated short-circuit making current (peak) | kA | 63/80 |
8 | Rated peak withstand current | kA | 63/80 |
9 | 4S short-time withstand current | kA | 25/31.5 |
10 | Rated operating cycle | O-0.1s – CO – 3s – CO – 6s CO- 60s recovery | |
11 | Rated short-circuit current breaking times | Times | 30 |
12 | Mechanical life | Times | 10000 |
13 | Mechanism control voltage | V | AC/DC220 |
14 | Secondary circuit 1min Power frequency withstand voltage | kV | 2 |