VSG/C-24 side-mounted indoor high-voltage vacuum circuit breaker is suitable for three-phase AC 50 (60) Hz, 24kV power system, for industrial and mining enterprises, power plants and substations as a switch between load current, overload current and fault current. It is suitable for frequent operation occasions. Widely used in power plants, power grids, petrochemicals, metallurgy, subways, airports, buildings and other projects.
Structural features
1. The circuit breaker adopts a modular operating mechanism and an integrated energy storage handle. The overall layout is reasonable, beautiful and simple;
2. The electrical components adopt a modular design, which is easy to disassemble and replace damaged electrical components;
3. The circuit breaker adopts solid-sealed poles, which improves the insulation performance of the circuit breaker;
4. High service life, the circuit breaker meets the M2 level of mechanical life and E2 of electrical life;
5. With excellent breaking performance, it can ideally fit inductive and capacitive loads;
Environmental conditions
1. Ambient temperature: upper limit +40°C, and the average value measured within 24 hours does not exceed 35°C; lower limit -15°C.
2. Altitude: no more than 1000m.
3. Relative humidity: the daily average value does not exceed 95%; the monthly average value does not exceed 90%;
4. Water vapor pressure: the daily average value does not exceed 2.2kPa, and the monthly average value does not exceed 1.8kPa;
5. The surrounding air is not obviously polluted by dust, smoke, corrosive or flammable gas, steam and salt spray
S/N | Item | Unit | Data | ||||
* | Type | / | 口Insulating cylinder
口Epoxy resin embedded poles 口Nylon embedded poles |
口Upper outlet
口Side outlet |
|||
1 | Rated voltage |
KV |
24 | ||||
2 | Rated short time power frequency withstand voltage(a min) | 65 | |||||
3 | Rated lightning impulse withstand voltage(peak) | 125 | |||||
4 | Rated frequency | Hz | 50 | ||||
5 | Rated current | A | 630
1250 |
630
1250
|
|||
6 | Rated short-circuit breaking circuit |
kA |
25 | 31.5 | |||
7 | Rated short time withstand current | 25 | 31.5 | ||||
8 | Rated short-circuit duration | s | 4 | ||||
9 | Rated peak withstand voltage |
kA |
63 | 80 | |||
10 | Rated short-circuit closing current | 63 | 80 | ||||
11 | Power frequency withstand voltage of secondary circuit(1 min) | V | 2000 | ||||
12 | Rated single / back-to-back capacitor bank breaking current | A | 630/400 | ||||
13 | Switching time |
ms |
20-50 | ||||
14 | Closing time | 35-70 | |||||
15 | Mechanical life |
time |
M2 level
10000(630-125-/25-31.5) |
||||
16 | Electrical life | E2 level | |||||
17 | Moving and fixed contacts allow wear accumulation thickness | mm | 3 | ||||
18 | Rated closing operating voltage | V | AC110, AC220
DC110, DC220 |
||||
19 | Rated breaking operating voltage | ||||||
20 | Rated voltage of energy storage motor | ||||||
21 | Rated power of energy storage motor | w | 90 | ||||
22 | Storage time | s | ≤15 | ||||
23 | Contact distance | mm | 13±1 | ||||
24 | Over stroke | 3±1 | |||||
25 | Contact closing bounce time |
ms |
≤2 | ||||
26 | Different phases of three-phase switching | ≤2 | |||||
27 | Average breaking speed |
M/s |
Contact opening 6mm | 0.9~1.7 | 0.9~1.7 | ||
28 | Average closing speed | Contact closing 6 mm | 0.6~1.0 | 0.6~1.0 | |||
29 | Switching rebound amplitude | mm | ≤3 | ||||
30 | Dominant loop resistance | μΩ | ≤45(630)
≤35(1250A) |
||||
31 | Contact closing pressure | N | 3100~3700 | ||||
32 | Rated order of operation | O-0.3s-CO-180s-CO |