GN22-12 (C) (D) series indoor high-voltage disconnector high-voltage switchgear is used in power systems with rated voltage of 12kV, 50Hz and below, to connect, disconnect or convert lines under voltage but no load.
Matching mechanism: Equipped with CS6-1, CS6-2 and other manual operating mechanisms, and electric operating mechanisms can also be used.
This series of switches are operated by CS6-2 manual operating mechanism or electric operating mechanism, and can be installed on the left or right side of the disconnector.
Structural features
This product is a high-current isolating switch with a three-phase common bottom knife structure. It adopts a mechanical locking prototype with a two-step action of closing and contacting, achieving wear-free contact, small operating force, high contact pressure, and good dynamic thermal stability.
Environmental conditions for use
1.Ambient air temperature: -15℃~40℃, daily average temperature ≦35℃.
2.Altitude ≦1000m.
3.Temperature conditions:
Daily average relative humidity ≦95%, daily average water vapor pressure ≦2.2kPa;
Monthly average relative humidity ≦90%, monthly average water vapor pressure ≦1.8kPa.
4.Earthquake intensity ≦8 degrees.
5.Places without fire, explosion danger, severe pollution, chemical corrosion and severe vibration.
Note: If the product use conditions exceed the above provisions, the user shall negotiate and determine with the company.
Application Areas:
Switchgear Systems: Used in metal-enclosed switchgear for isolating and protecting electrical circuits.
Power Distribution Equipment: Ideal for use in power substations, ensuring safe isolation of the circuit during maintenance.
Electric Power Plants: Utilized in indoor applications where high-voltage electrical isolation is required for safe operations and maintenance.
Transformer Stations: Applied in transformer substations for safe isolation of transformer circuits.
Renewable Energy Installations: Can be used in energy storage or renewable energy systems like solar and wind farms for protection and isolation during maintenance.
Model | Rated voltage | Rated current | 4-second thermal stability current (effective value) kA | Dynamic stability current (peak value) kA |
GN22-12(C)(D)/2000A | 12 | 2000 | 50 | 100 |
GN22- 12(C)(D)/2500A | 2500 | 50 | 125 | |
GN22-12(C)(D)/3150A | 3150 | 50 | 125 | |
GN22- 12(C)(D)/4000A | 4000 | 50 | 125 | |
GN22-12(C)(D)/5000A | 5000 | 100 | 250 | |
GN22- 12(C)(D)/6300A | 6000 | 100 | 250 | |
GN22- 12(C)(D)/8000A | 8000 | 100 | 250 |
Dimensional drawing reference (6300A)
Ordering instructions
●When ordering this switch, please indicate the model specification, rated voltage, rated current and other technical data.
●If there are special requirements, you can negotiate our to solve them.